TELEFIRE TPS-74A

Addressable Auxiliary Power Supply

Please log in or register to view prices.

Description

TELEFIRE TPS-74A

The TELEFIRE TPS-74A is an advanced addressable auxiliary power supply that is fed from a 230Vac input and includes a 24Vdc 100W power supply, battery charger, and a control card that monitors the TPS-74A and reports status and trouble information to the control panel. Reporting is done via the SLC loop and the TPS-74A takes up an address of the loop’s address range. The TPS-74A’s output is used when the total demand on the control panel’s 24Vdc power supply exceeds its capacity, or to power IO modules, sounders, or special detectors that are installed a long distance from the control panel.

Key Features

High-Power Supply: The TPS-74A’s 24Vdc output allows for up to .5A current draw during alarm. The power supply consists of a chassis that contains two 12V sealed lead-acid batteries in capacity of up to 14AH.

Addressable Supervision: Connects to control panels via SLC connection, allowing supervision of the auxiliary power supply’s status and faults. The address must be configured using the PROG-4000 programmer.

Intelligent Battery Management: Built-in battery charger and monitoring system that monitors AC voltage, battery charging/discharging and SLC communication with the control panel.

Flexible Installation: Should be installed in a closed location, avoiding exposure to outdoor environment to prevent high humidity, dust or air pollution.

Technical Specifications

  • Dimensions (W x H x D): 465 x 260 x 125 mm
  • Operating Temperature Range: -10°C to +60°C
  • Operating Voltage: 110-230Vac ±10% 50-60Hz
  • SLC Voltage: Maximum 21V modulated
  • 24Vdc to devices: Maximum .5A (UL 864 compliant)
  • Battery Capacity: Two 12V sealed lead-acid batteries, up to 14AH capacity
  • Battery Dimensions: Up to 14 W x .5 D x 17 H cm each

Installation Requirements

Cabling:

  • SLC Connection: Two-wire copper cable, 18 AWG cross section (.8 mm²), twisted-pair cable recommended
  • Maximum SLC Branch Length: 950 m for 18 AWG wire
  • 24Vdc Output: 2-wire cable, 12-18 AWG (.8-.3 mm²)

Power Supply: Connect to a dedicated circuit breaker that is not shared by other appliances or equipment. It is recommended that the circuit breaker shall be labeled “FIRE ALARM”.

Address Programming: Configure the power supply’s address using a TELEFIRE PROG-4000 programmer. Define as “Power Supply” type in the control panel.

LED Indications

  • OK (Red LED): Indicates that the power supply is addressed by the control panel1
  • TR (Yellow LED): Indicates a fault1
  • Charging (Red LED): On when the batteries are being charged1

When Auxiliary Power Supplies are Needed

For ADR-7000 Control Panels: Additional TPS-74A or TPS-34A auxiliary power supplies are required if at least one of the following conditions are met:

  • Current draw from the 24Vdc outputs is more than .5A in quiescent mode or .0A in alarm
  • The total power consumption of the control panel exceeds .0A in alarm
  • There is a requirement for batteries with more than 18AH capacity
  • Voltage drop to the last device exceeds 2V

For ADR-3000 Control Panels: Auxiliary power supplies are required if:

  • Current draw from the 24Vdc outputs is more than .5A in quiescent mode or .5A in alarm
  • The total power consumption exceeds .0A in alarm
  • There is a requirement for batteries with more than 14AH capacity

Certifications

  • UL 864 Approved
  • EN 54-4 Approved
  • EN 54-18 Approved

Compatible Systems and Products

Control Panels:

  • ADR-7000, SAVER-7000, GUARD-7 series control panels
  • ADR-3000 series control panels

Compatible Devices:

  • All TELEFIRE devices that require 24Vdc supply
  • TFB-180SA and TFB-180SBA horn bases
  • Various IO modules and addressable devices

Related products

  • TELEFIRE TPB-AKSA

    Switch to disable extinguishing cylinder for addressable control panel

    TELEFIRE TPB-AKSA

    Switch to disable extinguishing cylinder for addressable control panel

  • TELEFIRE TAU-700 címezhető letiltó egység – címzett eszközcsoportok ideiglenes letiltásához, LED visszajelzéssel, ADR-7000 és SAVER-7000 központokhoz.
    TELEFIRE TAU-700

    Addressable area neutralization unit

    TELEFIRE TAU-700 címezhető letiltó egység – címzett eszközcsoportok ideiglenes letiltásához, LED visszajelzéssel, ADR-7000 és SAVER-7000 központokhoz.
    TELEFIRE TAU-700

    Addressable area neutralization unit

  • TELEFIRE FRAME-SAVER

    Frames for SAVER Addressable control panel

    TELEFIRE FRAME-SAVER

    Frames for SAVER Addressable control panel

  • TELEFIRE FRAME-GUARD

    Frames for GUARD Addressable control panel

    TELEFIRE FRAME-GUARD

    Frames for GUARD Addressable control panel