TELEFIRE TAU-700

Addressable area neutralization unit

To display the price, please log in

Description

TELEFIRE TAU-700

The TELEFIRE TAU-700 is an addressable disabling unit designed to temporarily disable a group of addressable devices on TELEFIRE 7000 series fire alarm panels (ADR-7000, SAVER-7000). The device connects to the SLC loop, requires no separate 24VDC power supply, and supports three operating modes: short-circuit, disconnection, and normal operation. Its main application is in locations such as theaters where smoke machines are used and detectors must be temporarily disabled.

Key Features

  • Addressable control: Occupies two addresses on the panel (ADR-741 and ADR-805 cards).
  • Three operating modes: Short-circuit, disconnection, normal operation.
  • Application: For temporarily disabling a group of devices (e.g., stage, smoke machine use).
  • Simple integration: Connects to SLC loop, no need for separate 24VDC power.
  • Visual feedback: Disabling button with red LED indicator when active.
  • Central event reporting: The panel and sub-panels display a detailed disabling event message.
  • Timed reset: Disabling is set for a predefined period, after which normal operation resumes automatically.

Technical Specifications

  • Dimensions (AIB-800 enclosure): 167 x 125 x 33 mm
  • Operating temperature: -10°C – +60°C
  • Relative humidity: 10% – 93% (non-condensing)
  • Power supply: From SLC loop (21V modulated)
  • Current consumption: 200 μA (quiescent), 3.5 mA (disarmed)
  • Inputs: 1
  • EOL resistor: 100 Ω (EOL-20), disabling resistor: 3.9 kΩ
  • NFPA classification: Style 4 Class B
  • Certification: IS 1220

Installation and Programming

  • Address programming: Using PROG-4000 programmer or via the control panel PROG port.
  • Panel setup: Set ADR-805 card address to “Switch” type, ADR-741 card address to “Operating output”.
  • Labeling: Clearly label the device’s address and the disabled group on the unit.

Compatibility

  • Panels: ADR-7000, SAVER-7000 (not compatible with GUARD-7)
  • Programmer: PROG-4000

Related products

  • TELEFIRE TPS-74A

    Addressable Auxiliary Power Supply

    TELEFIRE TPS-74A

    Addressable Auxiliary Power Supply

  • TELEFIRE TPB-AKSA

    Switch to disable extinguishing cylinder for addressable control panel

    TELEFIRE TPB-AKSA

    Switch to disable extinguishing cylinder for addressable control panel

  • TELEFIRE DTH-800A

    Duct Detector Housing, base & Detector

    TELEFIRE DTH-800A

    Duct Detector Housing, base & Detector

  • TELEFIRE AIB-800

    Mounting box for I/O moduls

    TELEFIRE AIB-800

    Mounting box for I/O moduls