TELEFIRE TLD-R8
The TELEFIRE TLD-R8 is an 8-channel dry contact relay expansion module that mounts on the TLD-08 main board. This module enables the use of dry contact relays alongside the TLD-08’s open collector outputs, providing even more versatile control options. The TLD-R8 relays use the same addresses as the TLD-08 main board’s open collector outputs and are activated by the same logic conditions.
Key Features
8 Dry Contact Relays: The module contains 8 programmable dry contact relays that operate unsupervised and are not current limited.
Identical Addressing: The relays use the same 8 addresses as the TLD-08 main board’s open collector outputs and are activated by the same logic conditions.
Modular Design: The TLD-R8 mounts directly on the TLD-08 main board, providing a compact and integrated solution.
Programmable Activation Logic: The relay activation logic is programmable depending on the control panel configuration.
Technical Specifications
Relay Specifications:
- Number of Relays: 8 dry contact relays
- Supervision: Unsupervised, not current limited
- Activation Logic: Programmable
- Maximum Dry Contact Values: .5A 30Vdc
- Contact Type: NC (Normally Closed), C (Common), NO (Normally Open)
General Specifications:
- Operating Temperature Range: 0°C to 49°C
- Relative Humidity: 10% to 93% (non-condensing)
- Operating Voltage from SLC: 21V modulated
- Operating Voltage from Control Panel: 24Vdc nominal ±10%
Current Consumption (TLD-08 + TLD-R8 Configuration):
- SLC Line Quiescence Mode: 250µA
- SLC Line Alarm Mode: .5mA
- 24Vdc Supply Quiescence State: .5mA
- 24Vdc Supply Alarm State: .0mA
Configuration Options
The TLD-R8 used with the TLD-08 main board can occupy the following address ranges1:
Configuration Inputs OC Outputs Relays Address Range
TLD-08 + TLD-R8 None 8 8 4 or 8
Installation and Connection
Address Programming: The TLD-R8 does not require separate address programming as it uses the same addresses as the TLD-08 main board.
Control Panel Definitions: Define relay outputs as “Control Out” type in the control panel, with modes configurable as “Alarm”, “Fault”, “Fan”, “Damper”, or “Speaker” switching.
Wiring: Relay contacts are unsupervised and not current limited – suitable for same room connection only.
Safety Requirements
Voltage Limitation: Maximum 30Vdc voltage can be applied to relay contacts.
Installation Location: The module should be installed in a closed location, avoiding exposure to outdoor environment to prevent high humidity, dust, or air pollution.
Same Room Connection: Relay contacts are unsupervised, therefore suitable for same room connection only.
Certifications
- EN 54 Approved
- UL 864 Listed
- GOST Compliant
- CP 10 Compliant
- IS 1220 Approved
- CE Marked
Compatible Systems and Products
Control Panels:
- ADR-7000, SAVER-7000, GUARD-7 series analog addressable control panels
Main Board:
- TLD-08 Addressable Switch and Output Module (required)
Power Supplies:
- TPS-74A Auxiliary Power Supply for long-distance installation or high current consumption
Related products

TELEFIRE TSM-E16
Sixteen Switch Inputs Add-On for TLD-08

TELEFIRE TSM-E16
Sixteen Switch Inputs Add-On for TLD-08

TELEFIRE TLD-E16
Sixteen OC Outputs Add-On for TLD-08

TELEFIRE TLD-E16
Sixteen OC Outputs Add-On for TLD-08

TELEFIRE TLD-08
Eight OC Outputs Base Module

TELEFIRE TLD-08
Eight OC Outputs Base Module

TELEFIRE TFL-1AN
Auxiliary Signaling Indicator for Analog Address

TELEFIRE TFL-1AN
Auxiliary Signaling Indicator for Analog Address