Description
TELEFIRE TLD-08
The TELEFIRE TLD-08 is a versatile addressable IO module that provides multiple outputs and switch inputs for supervision and indication purposes. The module has a modular design and can be used in various configurations according to installation requirements. The TLD-08 main board contains 8 unsupervised open collector outputs and can optionally be expanded with additional cards.
Key Features
Modular Design: The TLD-08 family consists of a main card and optionally three different daughter boards:
- TLD-08 main board: SLC connectors, 24Vdc connectors, and 8 unsupervised open collector outputs
- TLD-E16: 16 open collector expansion module
- TLD-R8: 8 dry contact relay module
- TSM-E16: 16 switch input add-on module
Flexible Addressing: The module occupies 4, 8, 16, or 24 consecutive addresses, depending on hardware configuration and switch settings.
Programmable Operating Modes: Operating modes are selectable via switches or jumpers on the modules, including number of addresses or switch input modes.
Configuration Options
Configuration Inputs OC Outputs Relays Address Range
TLD-08 None 8 None 4 or 8
TLD-08 + TLD-E16 None 24 None 16 or 24
TLD-08 + TLD-R8 None 8 8 4 or 8
TLD-08 + TSM-E16 16 8 None 16 or 24
Technical Specifications
General Specifications:
- Operating Temperature Range: 0°C to 49°C
- Relative Humidity: 10% to 93% (non-condensing)
- Operating Voltage from SLC: 21V modulated
- Operating Voltage from control panel or auxiliary power supply: 24Vdc nominal ±10%
Current Consumption:
- SLC line quiescence mode: 250µA
- SLC line alarm mode: .5mA
- 24Vdc supply quiescence state: .5mA
- 24Vdc supply alarm state: .2mA to .0mA depending on configuration
TLD-08 Main Board Specifications
- Programmable Outputs: 8 open collector, unsupervised
- Output Type: Open collector, supplies minus
- NFPA Type: Class B
- Current Protection: Electronic
- Activation Logic: Programmable
- Maximum Line Impedance: 10Ω
- Maximum Current Each Output: 50mA
- Maximum Current All Outputs Concurrently: 280mA
Installation and Programming
Address Programming: Configure the module’s first address using a PROG-4000 device programmer or the control panel’s address programming port.
Control Panel Definitions:
- Inputs: Define as “Switch” type with various modes (Alarm, Reset, Silence, etc.)
- Outputs: Define as “Lamp”, “Supervisory Output”, or “Control Out” as appropriate
Cabling Requirements:
- SLC Connection: Two-wire copper cable, 12-20 AWG cross section (.5-.3 mm²)
- 24Vdc Supply: Fire-resistant cable, 12-20 AWG cross section
- Twisted-pair cable recommended
Installation Location
The module should be installed in a closed location, avoiding exposure to outdoor environment to prevent high humidity, dust, or air pollution.
Certifications
- EN 54 Approved
- UL 864 Listed
- GOST Compliant
- CP 10 Compliant
- IS 1220 Approved
- CE Marked
Compatible Systems and Products
Control Panels:
- ADR-7000, SAVER-7000, GUARD-7 series analog addressable control panels
Power Supplies:
- TPS-74A auxiliary power supply for long-distance installation or high current consumption
Expansion Modules:
- TLD-E16 expansion module (16 additional open collector outputs)
- TLD-R8 relay module (8 dry contact relays)
- TSM-E16 input module (16 switch inputs)
Related products

TELEFIRE TSM-E16
Sixteen Switch Inputs Add-On for TLD-08

TELEFIRE TSM-E16
Sixteen Switch Inputs Add-On for TLD-08

TELEFIRE TLD-R8
Eight Relay Add-On for TLD-08

TELEFIRE TLD-R8
Eight Relay Add-On for TLD-08

TELEFIRE TLD-E16
Sixteen OC Outputs Add-On for TLD-08

TELEFIRE TLD-E16
Sixteen OC Outputs Add-On for TLD-08

TELEFIRE TFL-1AN
Auxiliary Signaling Indicator for Analog Address

TELEFIRE TFL-1AN
Auxiliary Signaling Indicator for Analog Address