TELEFIRE TFH-60026WP

Heat Detector 194F Weather Proof

Features

TFH-60026WP Rate Compensation Heat Detector – All Weather

The TFH-60026WP is an all-weather, rate compensation heat detector designed for both indoor and outdoor use. This Model 302-ET type detector features hermetically sealed construction, making it suitable for moisture-proof and dust-proof installations. The device can be installed without a special back box and includes a plastic hexagonal grip bushing with 1/2″ conduit threads.

The detector operates on rate compensation principles, allowing for rapid temperature rise detection without the thermal lag issues characteristic of conventional fixed temperature detectors. The device consists of a high expansion aluminum tube containing two insulation struts with opposing open contact points.

Key Features:

  • Type: All-weather rate compensation heat detector (Model 302-ET)
  • Operating principle: Rate compensation
  • Temperature rating: 135°F (57°C) or 194°F (90°C)
  • Design: Hermetically sealed, moisture and dust proof
  • Installation: Indoor and outdoor use
  • Connection: 1/2″ conduit thread with plastic hexagonal grip bushing
  • Self-restoring: Yes, automatic reset when temperature drops

Technical Specifications:

  • Overall length: 4 1/8″
  • Base diameter: 2″
  • Electrical rating: 6-125 VAC / 5 amp, 6-25 VAC / 1 amp, 125 VDC / 0.5 amp
  • Maximum ceiling temperature: 115°F (135°F model), 155°F (194°F model)
  • Coverage area: 50′ x 50′ (2500 sq ft) on 8-10 ft ceilings
  • Directional sensitivity: None, can be mounted horizontally or vertically

Certifications:

  • UL (Underwriters Laboratories)
  • FM (Factory Mutual)
  • California State Fire Marshall
  • Listing No. 7270-0021001
  • MEA Acceptance 193-03-E

Application Areas:

  • Outdoor facilities
  • Wet or dusty environments
  • Industrial facilities
  • Warehouses and storage areas
  • Any area requiring weather-resistant detection

Important Notes:

  • Detectors, hub covers, or outlet boxes must never be installed in direct sunlight
  • Must be hand tightened only
  • Protect from direct sunlight and adverse weather conditions
  • Follow NFPA 72 standard for spacing and other considerations

Related products

  • TSA-240

    Conventional 4-Zone Extinguishing Control Panel

    TSA-240

    Conventional 4-Zone Extinguishing Control Panel

  • TSA-200

    Two zone fire alarm control panel

    TSA-200

    Two zone fire alarm control panel

  • TPB-10G

    Green manual push button designed to deactivate control for controlled doors during a fire / emergency event (single operation)

    TPB-10G

    Green manual push button designed to deactivate control for controlled doors during a fire / emergency event (single operation)

  • TFU-500

    Flame Detector DRD-E

    TFU-500

    Flame Detector DRD-E