TELEFIRE TDM-500ICN

Cellular Dialer

To display the price, please log in

Description

TELEFIRE TDM-500ICN

The TELEFIRE TDM-500ICN is an intelligent cellular dialer designed for use in fire, security, and safety detection systems to automatically dial and play pre-recorded voice messages during alarm and trouble events to emergency services and key personnel. The TDM-500ICN is the cellular version of the TDM-500i series, operating through mobile networks without requiring landline telephone connections.

The device is an advanced warning device ensuring maximum protection during fire events by swiftly dialing security forces or building owners through cellular connection. The device is compatible with various control panels, including addressable and zone-based systems, offering flexibility and ease of integration for installers.

Key Features:

  • Type: Intelligent cellular dialer device
  • Communication: Cellular (mobile network)
  • Operating voltage: 24V DC
  • Current consumption: 30 mA standby, 60 mA dialing
  • Dimensions: 167 x 125 x 33 mm
  • Weight: 310 g
  • Operating temperature: -10°C to +60°C
  • Relative humidity: 10-93% (non-condensing)

Programming Capabilities:

  • Manual programming or with TCS-7030 software through micro-USB cable
  • Separate phone lists and messages for two distinct events
  • Up to 10 phone numbers per event (optionally up to 32)
  • Up to 15-digit phone numbers
  • Digital display for phone numbers and control codes
  • Password protection for programming and recording

Communication Functions:

  • Dialing through cellular network
  • No landline telephone connection required
  • Optional RS-232 interface
  • Programmable delay
  • Reporting to fire alarm control panel

Performance Characteristics (according to EN 54-21:2006):

  • Transmission performance: D4, M4, T5
  • Operational reliability: A4 (99.8%)
  • Temperature resistance: Passed
  • Vibration resistance: Passed
  • Electrical stability: Passed
  • Humidity resistance: Passed

Compatible Systems:

  • TELEFIRE ADR-3000 analog addressable control panel
  • TELEFIRE TSA-1000, TSA-1000X, TSA-200, TSA-200X control panels
  • TELEFIRE GSA-1000, GSA-2B control panels
  • ADR-7000 series systems

Certifications:

  • EN 54-21:2006
  • CPR (Construction Products Regulation) EU 305/2011
  • ÉMI Certificate: 1415-CPR-115-C-69/2015

Related products

  • TELEFIRE TDM-500IN

    Wired dialer and Annunciator

    TELEFIRE TDM-500IN

    Wired dialer and Annunciator