Features
TELEFIRE BCF-10326 Smoke Release System
The BCF-10326 is a professional smoke release system manufactured by Telefire, capable of automatic and manual smoke extraction during fire events. The system’s reliable operation creates safe evacuation routes and effectively assists firefighting operations by removing smoke from the building in a timely manner.
Technical specifications
The BCF-10326 smoke release system consists of a BCF-10326 series control panel and motors installed in smoke windows and fire doors. The system is designed and operates according to the European standard EN-12101-2 and is approved by the Israel Standards Institute.
Control panel specifications
- Dimensions (W x H x D): 280 x 335 x 130 mm
- Operating temperature range: 0°C – 49°C
- Operating voltage: 220-240 VAC, 50 Hz
- Current output: 1-10 A
- Batteries: 2×12 V, up to 7 Ah
- Weight without batteries: 2 kg
Operating panel specifications
- Dimensions (W x H x D): 105 x 105 x 40 mm
- Operating temperature range: 0°C – 49°C
- Operating voltage: 220-240 VAC, 50 Hz
- Operating current: Up to 2.8 A
Operational capabilities
The BCF-10326 system is capable of communicating with addressable fire detection control panels from the 7000-3000 series and conventional control panels from the TSA series. During a fire event, the control panel sends a command to the smoke release system to open windows and doors for smoke extraction.
Motor support
- Standard model: supports up to 10 motors
- Extended model: supports up to 20 motors
- Up to 8 systems can be interconnected
The system operates with the following approved motors:
- BCF10329: Motor for tilt window N250 35 cm
- BCF10330: Motor for tilt window N250 40 cm
- BCF10331: Motor for tilt window N250 60 cm
- BCF10332: Linear actuator motor N300 50 cm
- BCF10333: Linear actuator motor N300 70 cm
- BCF10334: Linear actuator motor N300 100 cm
Installation and operation
The system can also be controlled by a manual control panel, which allows manual opening or closing of windows and doors. Windows can be opened using the OPEN button on the control panel, while they can be closed using the CLOSE button. The BCF-10326 smoke release system is designated for indoor use only.
Application areas
Smoke release systems can be installed in various buildings, including:
- Factories
- Event halls
- Wide and tall lobbies
- Sports halls
Maintenance
Semi-annual routine functionality checks must be performed on the system, which include:
- Manual window opening test using the OPEN button
- Manual window closing test using the CLOSE button
- Manual command from the fire detection control panel
- Error indication check
Certifications and compliance
The BCF-10326 system is certified according to SI 1220 standard. The system complies with Hungarian regulations and all operator interfaces are brought to market with Hungarian language labeling.
Compatible products and systems
- 7000 series addressable fire detection control panels
- 3000 series addressable fire detection control panels
- TSA series conventional control panels
- ADR-723 relay module
- ADR-741 addressable output module
Related products
TFLX-020
FAAST FLEX 2-pipe Stand-alone detector
TFLX-020
FAAST FLEX 2-pipe Stand-alone detector
TFLX-010
FAAST FLEX 1-pipe Stand-alone detector
TFLX-010
FAAST FLEX 1-pipe Stand-alone detector
TFB-EXB
TFB-EXB Base for Intrisically Safe Smoke Detector
TFB-EXB
TFB-EXB Base for Intrisically Safe Smoke Detector
TELEFIRE TSC-7000L
Firefighters Smoke-Control Station Expansion Module
TELEFIRE TSC-7000L
Firefighters Smoke-Control Station Expansion Module