Description
TELEFIRE TFB-180SA
The TELEFIRE TFB-180SA is an advanced analog addressable detector base with integrated horn functionality. This innovative device combines the functions of a standard detector base with an addressable horn, providing a compact and cost-effective solution for fire alarm systems1. The base is compatible with TELEFIRE’s analog addressable detector series and can be directly connected to the SLC line without requiring separate power supply.
Key Features
Integrated Horn: The TFB-180SA features a built-in addressable horn capable of producing various sound patterns according to control panel programming
Configurable Sound Patterns: Three switches allow setting of horn operation:
- Switch 1: Horn operation mode setting
- Switch 2: Volume control (high/low)
- Switch 3-4: Sound pattern selection
Available Sound Patterns:
- Constant sound 910Hz
- Rising sound from 500Hz to 1200Hz over 3.5 seconds
- Alternating sound between 910Hz and 685Hz at 2Hz frequency
- Intermittent sound half second 910Hz, half second pause
- Descending sound from 1200Hz to 500Hz per second
- Three pulses 500ms at 910Hz, then 1.5 second pause
- Up-down modulated sound every 0.5 seconds in 800-1000Hz range
- Rising sound from 800Hz to 970Hz per second
Addressable Control: The horn has a separate address and can be independently programmed in the control panel. The “Silenced Horn” function allows horn silencing from the control panel
Technical Specifications
- Diameter (including base): 124 mm
- Height (without detector): 58 mm
- Operating Temperature Range: -10°C to +60°C
- Relative Humidity: 10% to 93% (non-condensing)
- Operating Voltage: 20V modulated (from SLC line) + 24VDC (from panel or TPS-74A/TPS-34A power supply)
- Current Consumption from SLC line:
- Quiescent state: 180 µA
- Alarm state: 2 mA
- Current Consumption from 24VDC line:
- Quiescent state: 10 mA
- Alarm state: 22 mA
Installation and Programming
Address Programming: The horn address must be burned to the device card using PROG-4000 software or TFC-7000 technician kit. Address programming applies only to the horn; the detector has its own address
Control Panel Settings: The device must be set as “Silenced Horn” type in the control panel. This allows horn silencing while the detector continues to operate
Wiring: The device requires two types of power supply:
- SLC line for communication and detector power
- 24VDC line for horn power (from panel or external power supply)
Certifications
- IS 1220 Approved
Compatible Systems and Products
Control Panels:
- ADR-7000, SAVER-7000, GUARD-7
- ADR-3000
- ADR-SAVER
Compatible Detectors:
- TFO-480A Analog Addressable Optical Smoke Detector
- TFH-280A Analog Addressable Heat Detector
- TPH-482A Analog Addressable Combined Detector
Power Supplies:
- TPS-74A or TPS-34A Addressable Power Supplies
Related products

TELEFIRE TFGC-750
Carbon Monoxide (CO) Detector - Incl. Base

TELEFIRE TFGC-750
Carbon Monoxide (CO) Detector - Incl. Base
TELEFIRE TFB-180U
Standard Detector Base UL
TELEFIRE TFB-180U
Standard Detector Base UL
TELEFIRE TFB-180SBA
Addressable base-mounted sounder/strobe
TELEFIRE TFB-180SBA
Addressable base-mounted sounder/strobe
TELEFIRE TFB-180CA
Intrinsically Safely Base
TELEFIRE TFB-180CA
Intrinsically Safely Base